1. T-110 (5V Model)
T-110 is the world’s lightest and smallest CO2 sensor modules. Their easy management besides Persistent Stability and Temperature Effect Resistance are much favored by mobile application which needs sleep mode support, so on.
General Performance
Operating Temperature : 0 ~ 50℃
Operating Humidity : 0 ~ 95% RH (Non-condensing)
Operating Environment : Residential, Commercial spaces
Storage Temperature : -30℃ ~ 70℃
CO₂ Measurement
Sensing Method : NDIR (Non-dispersive Infrared)
Measurement Range : 400 ~ 2,000(3,000/5,000/10,000ppm, 2%/3%/5%/10% are available)
Accuracy : ±50ppm ±3% of reading (±300ppm ± 3% of reading - 2%/3%/5%/10% models)
Response Time (1/e) : 90 seconds
Sampling Interval : 5 seconds
Electrical Data
Power Input : 5.0V ± 5%
Current Consumption : Normal mode : 20mA, Peak : 200mA, Sleep: 0.5mA
Product Derivatives with Functions
| Products |
Option List |
| T-110L (Low Power) |
Sleep mode is added on T-110 for Low power, which consume < 0.5mA |
| T-110G (99%Humidity) |
Resistance up to 99% Humidity is added on T-110, for Application of bathroom |
| T-110LG |
Sleep mode + 99% Humidity |
| T-110A (ACDLS/W) |
Operate with ACDL S/W as default only for application of Residential Indoor Air Quality Monitoring which calibrate sensor every week by itself |
2. T-110-3V ( 3V Model )
T-110-3V is much favored by customers whose application needs 3.3Voltage input and sleep mode support so on.
General Performance
Operating Temperature : 0 ~ 50℃
Operating Humidity : 0 ~ 95% RH (Non-condensing)
Operating Environment : Residential, Commercial spaces
Storage Temperature : -30℃ ~ 70℃
CO₂ Measurement
Sensing Method : NDIR (Non-dispersive Infrared)
Measurement Range : 400 ~ 2,000(3,000/5,000/10,000ppm, 2%/3%/5%/10% are available)
Accuracy : ±50ppm ±3% of reading (±300ppm ± 3% of reading - 2%/3%/5%/10% models)
Response Time (1/e) : 90 seconds
Sampling Interval : 5 seconds
Electrical Data
Power Input : 3.2V ~ 3.55V
Current Consumption : Normal mode : 12mA, Peak : 180mA, Sleep: 0.2mA
Product Derivatives with Functions
| Products |
Option List |
| T-110L-3V (Low Power) |
Sleep mode is added on T-110-3V for Low power, which consume < 0.2mA |
| T-110G-3V (99%Humidity) |
Resistance up to 99% Humidity is added on T-110-3V, for Application of bathroom |
| T-110LG-3V |
Sleep mode + 99% Humidity |
| T-110A-3V (ACDLS/W) |
Operate with ACDL S/W as default only for application of Residential Indoor Air Quality Monitoring which calibrate sensor every week by itself |